DuPont ISCEON MO29 ISCEON® MO29 (R-422D) is an easy-to-use, non-ozone-depleting HFC refrigerant for replacing R-22 in medium-temperature direct expansion (DX) refrigeration applications (can also be used for low temperature), including commercial supermarket systems, and in stationary DX air conditioning applications, including DX water chillers.


Refer to Copeland's Changeover Guidelines, which now include R-22 to ISCEON® MO29 (R-422D) and ISCEON® MO79 (R-422A).


» ISCEON® MO29 Case Histories




Technical Literature
General

Safety and Handling


Retrofit Guidelines


Technical/Properties/Engineering




Product Information
ASHRAE #

R-422D

Replaces

R-22

Applications

  • Medium-temperature commercial and industrial DX refrigeration (can also be used for low temperature):
    • Food service
    • Supermarket display cases
    • Food storage and processing
    • Ice machines
  • Residential and commercial air conditioning:
    • Best choice for DX water chillers
Benefits

  • provides easy, quick, cost-effective retrofits -- easier retrofit than R-404A, R-507, and R-407C 
  • non-ozone-depleting HFC
  • in most cases no change of lubricant type during retrofit is required -- compatible with traditional and new lubricants
  • Field testing has been successful in many systems with no TXV change - superheat adjustment may be required.
  • An assessment of TXV loading is required to determine if TXV change is required
  • enables continued use of existing equipment
  • 30% lower Global Warming Potential (GWP) vs. R-404A and R-507
  • after retrofit, can be topped off during service without removing the entire refrigerant charge
Performance

  • closest match to R-22 capacity and efficiency in most systems
  • significantly lower discharge temperature vs. R-22 - likely to prolong the life of the compressor
  • provides up to 8% improved cooling capacity and up to 14% improved efficiency vs. R-22 at low-temperature conditions
  • provides slightly lower cooling (about 5%) capacity and comparable efficiency vs. R-22 at medium-temperature conditions with 10°F (6°C) subcooling
Phaseout Schedule

ISCEON® MO29 is a zero ozone-depleting substance (ODS) and, therefore, is not subject to phaseout under the Montreal Protocol regulations.

Lubricants Recommendation

ISCEON® MO29 is compatible with traditional and new lubricants-- mineral oil (MO), alkylbenzene (AB) and polyol ester (POE) -- in most cases no change of lubricant type during retrofit is needed.  Refer to the ISCEON® MO29 Retrofit Guidelines and Copeland's changeover guidelines, which now include ISCEON® MO29 & ISCEON® MO79, for additional information.

ASHRAE Safety Classification

A1

Cylinder Sizes

See specific container size information in your country or region.

 Where to Buy
Find a Distributor


 Refrigerants by Country
Select a Country/Region


 Related Links
ISCEON® Case History Library

Environmental & Regulatory Updates

DuPont MSDS Central

Related Resources


 Print PagePrint Page  Contact | FAQ | Site Map | Search
 © 1995 - 2008. DuPont. All Rights Reserved. The DuPont Oval, DuPont™, The miracles of science™ and all products denoted with ™ or ® are trademarks or registered trademarks of DuPont or its affiliates.

Legal Notices & Terms of Use | PRIVACY
 Do you have an upgrade or comment about this page?

Please contact Corporate Information Center. Thank you for your feedback!